View Rslogix 500 Analog Input Scaling PNG

View Rslogix 500 Analog Input Scaling PNG. Scaling an analog signal in rslogix 5000 through cpt. However, it’s just as easy.

How to Upload Siemens PLC Programs? - InstrumentationTools
How to Upload Siemens PLC Programs? - InstrumentationTools from cdn.instrumentationtools.com
For more information about the slc 500, visit the slc 500 category page! In this example, the analog input module is set up to place a value of 4000 to 20000 into the input data table. For this example, that would be 0 to 200psi.

Scaled value = (input value x rate) + offset.

Since we see above the value we are getting is 12000, that is exactly half way between 4000 and 20000. Do you need rslogix to use function block diagrams? The scaled min and max is the engineering units of the transducer. Mar 29, 2021 · scaling analog input rslogix 500 for example, an electronic system reads the number 15 as “1111”.